Level 1 Β· Free project

Commission the transfer-pump starter

Lock out, prove dead, wire the control circuit to the PLC, restore power and run the pump. A 415 V DOL starter with a 24 V PLC, built the way industrial panels are.

Free with a free account. Runs in your browser.

The circuit diagram of the panel, as drawn in the lab: Commission the transfer-pump starter
The closed cabinet door with its lamps, buttons and isolator handle, as drawn in the lab: Commission the transfer-pump starter

What you will build

Work order WO-PS-101. Your site team, Commission the P-101 transfer-pump starter.

The starter panel for transfer pump P-101 has arrived from the panel shop with the power circuit and the 24 V supply wired. The control wiring to the PLC is yours.

What you will learn

  • Lock out and prove dead, live then dead then live
  • Land 19 control conductors from a wiring schedule
  • Read the supplied PLC program and match it to your wiring
  • Restore power safely, test, and run the FAT

How it goes

  1. Lock out the panel at the main isolator Q1: switch OFF, apply your lock and your tag.
  2. Prove it dead with the meter, live-dead-live: prove the meter on the live incoming terminals, check every conductor on the load side reads 0 V, prove the meter again.
  3. Wire the 19 conductors of the wiring schedule. One conductor per terminal: X2 has spare bridged terminals for +24 V (1 to 6) and 0 V (7 to 12).
  4. Read the supplied PLC program. You may improve it, but the tag addresses must match your wiring.
  5. Restore power: tick the checklist, remove your tag and lock, switch Q1 ON, put the PLC in RUN.
  6. Test: START runs the pump and fills the day tank, STOP and the E-STOP stop it, an overload trip stops it and lights TRIP, and nothing restarts by itself. Then run the FAT.

Parts in the panel

  • Main isolator, 4-pole, 63 A

    Switches all three phases and neutral. The incoming cable lands on 1, 3, 5, 7: those terminals stay live when it is OFF.

  • MCB 2-pole, 6 A, C curve: control supply

    Feeds the 24 V power supply with 230 V (L1 and N).

  • MCB 3-pole, 16 A, D curve: motor circuit

    Protects the motor circuit against short circuits. The overload relay protects the motor against overload.

  • Contactor 3-pole, 9 A AC-3, coil 24 V DC, 1 NO aux

    Switches the motor. Coil A1(+)/A2(βˆ’). The 13 to 14 auxiliary contact tells the PLC the contactor really pulled in.

  • Thermal overload relay, 5.5 to 8 A

    Trips on sustained overcurrent. 95 to 96 (NC) opens and 97 to 98 (NO) closes. Blue button: reset.

  • Power supply 230 V AC to 24 V DC, 5 A

    Its 0 V (βˆ’) is bonded to PE at the factory, so 0 V and earth are the same potential.

  • PLC: compact CPU, 8 DI / 6 DQ, 24 V DC

    Inputs I0.0, I0.7 are PNP: 24 V on the terminal turns the input on, with 1M at 0 V. Outputs Q0.0, Q0.5 source 24 V from 3L+.

  • Terminal strip X2: 24 V DC distribution

    Positions 1 to 6 are bridged +24 V, 7 to 12 are bridged 0 V. Top and bottom of each position are the same point.

  • Terminal strip X1: motor

    The motor cable from the plant lands here.

  • PE bar

    Protective earth, bonded to the incoming supply's earth.

  • Push button START, green, 1 NO

  • Push button STOP, red, 1 NC

  • Emergency stop, 2 NC, twist to release

    Contact 11 to 12 is hardwired in the coil circuit; 21 to 22 tells the PLC.

  • Pilot lamp green 24 V: RUNNING

  • Pilot lamp amber 24 V: OVERLOAD TRIPPED

  • Motor 3-phase 2.2 kW, 415 V, 4.6 A, driving pump P-101

Questions

Is it free?
Yes. The lab is free to use with a free account. There is nothing to buy to open this scenario.
Do I need to install anything?
No. It runs in your browser with a 3D panel, a circuit drawing, a meter and a PLC.
What will I do in Panel Lab 1?
You wire a control panel, then check your work against an acceptance test.
How long does it take?
Plan for one sitting. You can stop and come back.
Do I need experience?
No. Each work order says what to do step by step, and hints are there if you get stuck.